OM-4435 Page 49
B. Standard Generator Power
Trouble Remedy
No generator power output at AC recep-
tacles; weld output okay.
Reset receptacle supplementary protectors (see Section 7-1).
No generator power or weld output. Disconnect equipment from generator power receptacles during start-up.
Check fuse F1, and replace if open (see Section 8-10). Have Factory Authorized Service Agent check
field excitation circuit.
Reset supplementary protector CB3 (see Section 8-10).
Check Voltmeter/Ammeter help displays (see Section 8-11).
Have Factory Authorized Service Agent check brushes and slip rings, and field excitation circuit.
High output at generator power AC re-
ceptacles.
Have Factory Authorized Service Agent check field excitation circuit.
Low output at generator power AC re-
ceptacles.
Check engine speed, and adjust if necessary.
Check fuse F1, and replace if open (see Section 8-10). If F1 is open, have Factory Authorized Service
Agent check the rotor.
C. Engine
Trouble Remedy
Engine will not crank. Check battery, and replace if necessary.
Check battery connections and tighten if necessary.
Circuit breaker CB1 may be open. CB1 automatically resets when fault is corrected (see Section 8-10).
Have Factory Authorized Service Agent check engine wiring harness and components.
Reset supplementary protector CB2 (see Section 8-10).
Check engine wiring harness plug connections.
Have Factory Authorized Service Agent check Engine Control switch S1, Fuel/Hour gauge FUEL/HM,
and control relay CR2.
Engine cranks but does not start. Check fuel level.
Check battery and replace if necessary. Check engine charging system according to engine manual.
Have Factory Authorized Service Agent check control relay CR1, Fuel/Hour gauge FUEL/HM, fuel
solenoid FS1, and the fuel pump.
Air in fuel system. See engine manual.
Engine hard to start in cold weather. Use Preheat switch S4 (see Section 6-2).
Keep battery in good condition. Store battery in warm area off cold surface.
Use fuel formulated for cold weather (diesel fuel can gel in cold weather). Contact local fuel supplier for
fuel information.
Use correct grade oil for cold weather (see Section 8-1).
Have Factory Authorized Service Agent check Preheat switch S4, control relay CR3, and the glow
plug.
Engine suddenly stops. Check oil and coolant levels. Automatic shutdown system stops engine if oil pressure is too low or coolant
temperature is too high (see Section 5-8 ).
Check fuel/hour meter for indication of shutdown.
Reset supplementary protector CB2 and/or clear fault causing circuit breaker CB1 to trip (see Section
8-10). Have Factory Authorized Service Agent check engine alternator, engine harness, fuel solenoid
FS1, and the fuel pump.
Have Factory Authorized Service Agent check Engine Control switch S1, control relay CR1, inte-
grated rectifier SR2, fuel solenoid FS1, and the fuel pump.
See engine manual.